COMMERCIAL FIRE INSPECTION - 1527 E SAN MARNAN DR-
10/02/26
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 1
OCCUPANCY FEE
$40.00
$10.00
CUSTOMER #
12579
BILLING DATE
10/12/2026
DUE DATE
11/16/2026
City of Waterloo
INVOICE #
2027-00000181
Less Prepayment
Total Due
CHARGES
$50.00
$0.00
$50.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
immy John's - 1527 E San Marnan DR, BLDG 1527 E San Marnan Dr, Waterloo IA
50702
INSPECTION DETAILS
Inspection Date
10102/2026
Lead Inspector
BRAD BALDWIN
Inspection Type s-
Annual Inspection (IYr) , p�
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
24535
Shift Station Unit
N/A NIA NIA
SUMMARY OF INSPECTION
0 32
Passed codes
NEXT STEPS
0 5
Failed codes
® 37
N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 10102/2026 @ 15:34
Reinspection Date
11/0412026
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 10/02/2026 @ 15:34
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#0) - Cell: 319-230-1224
BRAD BALDWIN - 10/02/2026 @ 15:34
• $50 annual inspection fee
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Sarah Villarreal 2026 (district)
CHECKLISTS
-L
Date: BRAD BALDWIN 10/02/2026
GENERATED ON 10/2/26, 3;36 PM 1 OF 4
Electrical Safety
Status Code
Fail 603.2 • Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that Is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Fail 603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Fire Resistant Construction Maintenance
Status Code
Fail 704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
rooflceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Description
Location: Above slicing area
Comments: Wiring damaged hanging from ceiling shall be repaired.
Location: Light fixture above register
Comments: Per staff present during 1012126 inspection: Light
flickering due to possible water damage shall be repaired.
Description
Location: Kitchen & back stock area
Comments: All missing ceiling tiles shall be replaced.
GENERATED ON L0/2/26, 3:36 PM
2 OF 4
Portable Fire Extingusihers
Status Code
Fail
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained In accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10, 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
906.7 - Hangers and brackets.
Hand-held portable fire extinguishers, not housed in cabinets,
shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturer's
installation instructions.
Description
Location: Fire extinguishers (2)
Comments: Provide annually serviced extinguishers in required
locations. Contractor shall tag current date of service, or tape receipt
of purchase to bottom if self -purchasing.
Location: Extinguishers
Comments: Annually serviced extinguishers shall be mounted on
wall brackets from 4" to 5' off the floor in height. Currently
extinguishers sitting on ground due to faulty brackets
GENERATED ON 10/2/20, 3:30 PM