COMMERCIAL FIRE INSPECTION - 2410 CROSSROADS BLVD-
10/06/26
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 20,000
OCCUPANCY FEE
$90.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
25100
10/12/2026
11/16/2026
2027-00000171
$100.00
Less Prepayment
Total Due -*
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Neighborhood Home - 2410 Crossroads BLVD, BLDG 2410 Crossroads Blvd,
Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
1010612026
Inspection Type
Annual Inspection (1Yr)
425 E. 3rd Street
3 3-66r LI, C,
Inspection Number
a S 10 b 4 1 r .�° 24566
Lead Inspector Shift
BRAD BALDWIN NIA
Other Inspectors
NIA
Station
NIA
Unit
NIA
SUMMARY OF INSPECTION
0 35 ® 22 ®26
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
Reinspection Date
11/0612026
BRAD BALDWIN - 1010612026 @ 07:51
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN -1010612026 @ 07:51
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#0) - Cell: 319-230-1224
BRAD BALDWIN - 1010612026 @ 07:51
• $100 annual inspection fee
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Brody Knutson 2026
CHECKLISTS
Date: BRAD BALDWIN 10107/2026
GENERATED ON 10/7/20, 2:35 PM
1 OF 10
Additional Codes
Status Code
Fail
Fail
1010.2 - Door operations.
Except as specifically permitted by this section, egress do )rs
shall be readily openable from the egress side without the
use of a key or special knowledge or effort.
1010.2.1 - Unlatching.
The unlatching of any door or leaf for
egress shall require not require more than one operation
motion in a single linear or rotational direction to release all
latching and all locking devices. Exceptions: 1.Places of
detention or restraint. 2.Where manually operated bolt locks
are permitted by Section 1010.2.5. 3.Doors with automatic
flush bolts as permitted by Section 1010.2.4, Item 3 4. 4.Doors
from individual dwelling units and sleeping units of Group R
occupancies as permitted by Section 1010.2.4, Item 4 5.
Descrip1 on
Location: Dock (interior) door
Comments: Remove key lock from door.
Location: Dock (exterior) exit door
Comments: Required exit doors shall not include more than a single
motion to unlock and unlatch door to exit, currently two motions
exist. Corrections shall be made to comply with exit door
requirements. Replacement of required exit door or lock/latch
hardware requires permit and inspection.
GENERATED ON 10/7/26, 2:35 PM
2 OF 10
Fall
0
1010.2.4 - Locks and latches.
Locks and latches shall be permitted to prevent operation of
doors where any of the following exist: S.Places of detention
or restraint. 2.In Group 1-1, Condition 2 and Group 1.2
occupancies where the clinical needs of persons receiving
care require containment or where persons receiving care
pose a security threat, provided that all clinical staff can
readily unlock doors at all times, and all such locks are keyed
to keys carried by all clinical staff at all times or all clinical
staff have the codes or other means necessary to operate the
locks at all times. 2. 3. In buildings In occupancy Group A
having an occupant load of 300 or less, Groups B, F, M and S,
and in places of religious worship, the main door or doors are
permitted to be equipped with key -operated locking devices
from the egress side provided: 2.1. 3.1. The locking device is
readily distinguishable as locked. 2.2.3.2. A readily visible
durable sign is posted on the egress side on or adjacent to
the door stating: "THIS DOOR TO REMAIN UNLOCKED WHEN
THIS SPACE IS OCCUPIED." The sign shall be In letters 1 inch
(25 mm) high on a contrasting background. 2.3. 3.3. The use
of the key -operated locking device is revocable by the fire
code official for due cause. 3.4. Where egress doors are used
in pairs, approved automatic Rush bolts shall be permitted to
be used, provided that the door leaf having the automatic
flush bolts does not have a doorknob or surface -mounted
hardware. 4. 5. Doors from individual dwelling or sleeping
units of Group R occupancies having an occupant load of 10
or less are permitted to be equipped with a night latch, dead
bolt or security chain, provided such devices are openable
from the inside without the use of a key or tool. 5. 6. Fire
doors after the minimum elevated temperature has disabled
the unlatching mechanism in accordance with listed fire door
test procedures. 6. 7. Doors serving roofs not intended to be
occupied shall be permitted to be locked, preventing entry to
the building from the roof. 8.Other than egress courts, where
occupants must egress from an exterior space through the
building for means of egress, exit access doors shall be
permitted to be equipped with an approved locking device
where installed and operated in accordance with all of the
following: 8.1.The maximum occupant load shall be posted
where required by Section 1004.9. Such sign shall be
permanently affixed inside the building and shall be posted in
a conspicuous space near all the exit access doorways. 8.2.A
weatherproof telephone or two-way communication system
installed in accordance with Sections 1009.8.1 and 1009.8.2
shall be located adjacent to not less than one required exit
access door on the exterior side. 8.3.The egress door locking
device is readily distinguishable as locked and shall be a key -
operated locking device. 8.4.A clear window or glazed door
opening, not less than 5 square feet (0.46 m2) in area, shall
be provided at each exit access door to determine if there are
occupants using the outdoor area. 8.5.A readily visible
durable sign shall be posted on the interior side on or
adjacent to each locked required exit access door serving the
exterior area stating: "THIS DOOR TO REMAIN UNLOCKED
WHEN THE OUTDOOR AREA IS OCCUPIED." The letters on
the sign shall be not less than 1 inch (25.4 mm) high on a
contrasting background. 8.6.The occupant load of the
occupied exterior area shall not exceed 300 occupants In
accordance with Section 1004. 9.Locking devices are
permitted on doors to balconies, decks or other exterior
spaces serving individual dwelling or sleeping units.
10.Locking devices are permitted on doors to balconies,
decks or other exterior spaces of 250 square feet (23.23
m2) or less, serving a private office space.
Location: North and East exit doors
Comments: Provide permanent approved signage indicating "THIS
DOOR SHALL REMAIN UNLOCKED WHILE OCCUPIED" or other
approved wording on exterior exit doors. Laminated paper will not be
accepted.
GENERATED ON 10/7/24, 2:05 PM 3 OF 10
Fail
901.4.7.2 - Marking on access doors.
Access doors for automatic sprinkler system riser rooms and
fire pump rooms shall be labeled with an approved sign. The
lettering shall be in contrasting color to the background.
Letters shall have a minimum height of 2 inches (51 mm) with
a minimum stroke of 3/8 inch (10 mm).
Fire Alarm System
Status
Fail
Code
Chapter 14 - Inspection, testing, and maintenance
Fire alarm system tested at least annually by licensed
contractor
Fire Sprinkler System
Status
Fail
Code
5.2.1 - Annual sprinkler system inspection
Sprinklers shall be inspected at least annually by licensed
contractor
Location: West exterior door - Sprinkler Riser Room
Comments: Permanent approved signage shall be installed on
exterior side of door indicating "FACP" and "SPRINKLER RISER".
Signls shall include red background with white lettering. Laminated
paper will not be accepted as permanent.
FIRE ALARM
CONTROL PANEL
SPRINKLER
RISER ROOM
Description
Location: Fire Alarm
Comments: Licensed alarm contractor shall complete annual
inspection and upload report to Compliance Engine including
deficiencies corrected. Currently no record of last inspection.
Description
Location: Sprinkler system
Comments: Required annual inspection by licensed contractor shall
be completed with report including deficiencies corrected to be
uploaded to Compliance Engine. Last recorded inspection on 8/28123
GENERATED ON 10/7/20, 2:35 PM 4 OF 10
Fire Service Features
Status Code
Fall
Fail
Fail
Fail
506.2 - Key box maintenance.
The operator of the building shall immediately notify the fire
code official and provide the new key where a lock is changed
or rekeyed. The key to such lock shall be secured in the key
box.
509.1- Identification.
Fire protection equipment shall be identified in an approved
manner. Rooms containing controls for air-conditioning
systems, sprinkler risers and valves, or other fire detection,
suppression or control elements fire protection systems shall
be identified for the use of the fire department. Approved
signs required to identify fire protection system equipment
and equipment location shall be constructed of durable
materials, permanently installed and readily visible.
509.2 - Equipment access.
Approved access shall be provided and maintained for all fire
protection system equipment to permit immediate safe
operation and maintenance of such equipment. Storage, trash
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
509.2 - Equipment access.
Approved access shall be provided and maintained for all fire
protection system equipment to permit immediate safe
operation and maintenance of such equipment. Storage, trash
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
Description
Location: Knox Box
Comments: Contact Waterloo Fire Dept at 319.291.4460 to update all
required keys in Knox Box. Keys to Sprinkler Riser room shall be
included.
Location: Sprinkler riser room
Comments: Interior door separating Riser Room and Fire Alarm
Control Panel shall have permanent approved "FACP" signage
installed on Riser Room side. Laminated paper will not be accepted.
FACP
Location: Sprinkler Riser Room
Comments: Remove storage within 36" of sprinkler system and
maintain clear path of access for fire fighters at all times.
Location: Fire Alarm Panel
Comments: Remove storage of doors and all obstructions within 36"
of alarm panel and maintain clear ready access to panel at all times.
GENERATED ON 10/7/26, 2:35 PM 5 OF 10
Electrical Safety
sra_lis code
Fail
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Description
Location: Behind "Flexsteel Linden" couch
Comments: Licensed electrician shall make necessary repairs to
damaged receptacle (see photo). Retain copy of invoice from
electrician for inspector. Also, remove extension cord.
GENERATED ON 10/7/26, 2:35 PM 6 OF 1e
Fail
Fail
Fail
Fail
603.2 • Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment, Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70,
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Location: Recliner post near register area
Comments: Provide knockout plug for opening in box
Location: Lift chair area
Comments: Replace missing outlet cover below painting.
Location: Sales floor - Behind "5Z Pittson Anchor" couch
Comments: Replace missing outlet cover
Location: Utility Room
Comments: Remove storage within 36" of electric panels and
equipment, maintain proper clearances at all times.
GENERATED ON 10/7/25, 2:35 PM
7 OF 10
Fail 603.4.1- Labeling.
Doors into electrical control panel rooms shall be marked
with a plainly visible and legible sign stating "ELECTRICAL
ROOM" or similar approved wording. The disconnecting
means for each service, feeder or branch circuit originating
on a switchboard or panelboard shall be legibly and durably
marked to indicate its purpose unless such purpose is clearly
evident. Where buildings or structures are supplied by more
than one power source, markings shall be provided at each
service equipment location and at all interconnected electric
power production sources identifying all electric power
sources at the premises in accordance with NFPA 70.
Fail
Fail
Fail
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Main electric room 1 Sprinkler Riser Room
Comments: Permanent approved signage shall be installed Indicating
"ELECTRIC ROOM" or other approved wording on or near interior
door.
Location: Lift chair area
Comments: Remove extension cord. may replace with properly
supported power strip with manual reset for low wattage electronics
only.
Location: Adjustable base area
Comments: Remove extension cord.
Location: Sales floor - Display west of north exit door
Comments: Remove extension cord. may replace with properly
supported power strip with manual reset for low wattage electronics
only.
Location: Sales floor - Desk area
Comments: Remove red extension cord and power strip in extension
cord. Power strips shall plug directly to an outlet.
GENERATED ON 10/7/25, 2,35 RN
eori-
Portable Fire Extingusihers
Status
Fail
Fail
O
Code Description
906.2 • General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A•5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
906.6 - Unobstructed and unobscured.
Portable fire extinguishers shall not be obstructed or
obscured from view. In rooms or areas in which visual
obstruction cannot be completely avoided, means shall be
provided to indicate the locations of extinguishers.
Location: Entire building
Comments: Provide required annual service to all extinguishers in
building. Last serviced in June 2022
Location: Utility Room
Comments: Remove storage obstructing ready access to
extinguisher.
OENEPATED ON 10/7/26, 2:35 PM
9 OF 10