COMMERCIAL FIRE INSPECTION -1535 FLAMMANG ST-09/22/26
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
CUSTOMER #
15391
BILLING DATE
DUE DATE
INVOICE #
Total Price
CHARGES
$70.00
$10.00
10/14/2026
11/20/2026
2027-00000193
$80.00
City of Waterloo
Less Prepayment
Total Due
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Hibachi Sushi Buffet • 1535 Flammang DR, BLDG 1535 Flammang Dr, Waterloo IA
50702
INSPECTION DETAILS
Inspection Date
09122/2026
Inspection Type
Annual Inspection (1Yr)
Lead Inspector Shift
BRAD BALDWIN NIA
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
24376
Station Unit
N/A NIA
SUMMARY OF INSPECTION
0 51 0 19
0 15
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 09122/2026 @ 14:27
Fire extinguishers due annually serviced April 2027
BRAD BALDWIN - 0912212026 @ 14:26
Annual sprinkler inspection due 1017126. Report to be uploaded to Compliance Engine
BRAD BALDWIN - 0912212026 @ 14:25
Kitchen hood exhaust suppression system due for inspection on 10/14/26. Report to be uploaded to Compliance Engine
BRAD BALDWIN - 09/2212026 @ 14:24
Kitchen hood exhaust cleaning due 10/16/26. Report to be uploaded to Compliance Engine
Reinspection Date
10123/2026
BRAD BALDWIN - 09122/2026 @ 14:24
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 09122/2026 @ 14:24
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291.4319 (#0) - Cell: 319-230-1224
BRAD BALDWIN - 0912212026 @ 14:24
• $80 annual inspection fee
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
GENERATED ON 9/24/26, 2:50 PM 1 OF 7
Wen xu - 2026 Date: _ BRAD BALDWIN 0912412026
CHECKLISTS
Means of Egress
Status Code
Fail
1032.3 - Obstructions.
A means of egress shall be free from obstructions that would
prevent its use, including the accumulation of snow and ice.
Description
Location: West exit near bathrooms
Comments: Trim trees and bushes over -growing sidewalk outside
exit door
GENERATED ON 9/24/26, 2:50 PM
2 OF 7
Emergency Equipment
Stat rs Code
Fail
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
Fail 1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
Fail 1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
Fail 1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
Fail 1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
Description
Location: Near hostess stand
Comments: Repair or replace egress Tight that failed to Illuminate
during test.
Location: West dining area - above soda fountain machine
Comments: Repair or replace egress Tight that failed to illuminate
during test.
Location: Bathroom hallway
Comments: Repair or replace egress light that failed to illuminate
during test.
Location: Mens bathroom
Comments: Repair or replace egress light that failed to illuminate
during test.
Location: Wornens bathroom
Comments: Repair or replace egress light that failed to illuminate
during test.
Location: Above "Cut Table"
Comments: Repair or replace egress light that failed to illuminate
during test.
Location: Kitchen - near fryers
Comments: Replace missing egress light
GENERATED ON 0/24/20, 2:50 PM
3 OF
Fail 1203.2.15 - Means of egress Illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008,3 and 1104.5,1.
Fail
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
General Housekeeping
Fail
304.3.1- Spontaneous ignition.
Materials susceptible to spontaneous ignition, such as oily
rags, shall be stored in a listed disposal container. Contents
of such containers shall be removed and disposed of daily.
Fire Sprinkler System
Fail
5.2.1.1.5 - Missing escutcheons
Escutcheons and coverplates for recessed, flush, and
concealed sprinklers shall be replaced if found missing
during the inspection.
Additional Codes
Fail
Location: East dining area - above soda fountain machine
Comments: Repair or replace egress light that failed to illuminate
during test.
Location: Main exit doors
Comments: Repair or replace exit sign that failed to illuminate during
test.
Description
Location: Kitchen
Comments: Provide listed container with self -closing lid for disposal
of soiled rags, remove from building daily.
Description
Location: "Lobby" dining area - Near south dining exit door
Comments: Sprinkler escutcheon shall be repaired to be flush with
ceiling.
Corte Description
504.1 - Required access.
Exterior doors and openings required by this code or the
International Building Code shall be maintained readily
accessible for emergency access by the fire department. An
approved access walkway leading from fire apparatus access
roads to exterior openings shall be provided where required
by the fire code official.
Location: Kitchen storage - Roof access ladder
Comments: Remove storage blocking clear access to ladder,
maintain area around ladder clear to access at all times.
OENEPATEO ON 9/74/26, 2:50 PM
4 OF 7
Electrical Safety
Status Cork
Fall
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open Junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Description
Location: Kitchen • North exit
Comments: Licensed electrician shall repair MC cable and wire
connection to exit sign.
Location: Sprinkler riser room
Comments: Electric box and equipment below (see photo) missing
covers exposing wires shall be corrected.
GENERATED ON 9/24/26, 2:50 PM
5 OF 7
Fail
Fail
Fail
603.5.2 - Application and usePower supply.
Relocatable power taps and current taps shall be directly
connected to a permanently Installed receptacle. Exceptions:
1. Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Commercial Cooking Hood Suppression System
STdTUS Cotle
Fail
606.3.3.1- Inspection.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be inspected at intervals specified in
Table 606.3.3.1 or as approved by the fire code official.
Inspections shall be completed by qualified individuals.
Location: Office
Comments: Remove power strip plugged to another power strip
behind computer. Each power strip shall plug directly to a wall outlet.
Location: Pepsi fridge near sushi cooler
Comments: Provide cord protector for appliance cord across
walkway or relocate appliance to avoid possible damage to cord.
Location: Kitchen - near fryers
Comments: Extension cord extending above drop ceiling shall be
removed.
Description
Location: Hibachi Grill
Comments: Grill gas supply shall be disconnected from appliance
and capped.