COMMERCIAL FIRE INSPECTION- 3610 ANSBOROUGH AVE- FOR BILLING INQUIRY: (319)291-4323
10/13/26
Description Total Price
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
11638 10/20/2026 11/24/2026 2027-00000200 $100.00
Less Prepayment $0.00
Total Due -* $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
;i ` `° Inspection Report
425 E.3rd Street
Community United Child Care-3610 Ansborough AVE,BLDG 3610 Ansborough
Ave,Waterloo IA 50701
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
10/13/2026 Annual Inspection(1Yr) I, / -41°0 ,DO 19614
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
42 G 12 ® 26
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspectian Date
BRAD BALDWIN
11/1312026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-10/16/2026 @ 07:38
Christmas lighting approved for temporary usage(90 days).Lighting shall be removed after 90 days expires.
BRAD BALDWIN-10/1612026 @ 07:37
Extinguishers due annually serviced June 2027
BRAD BALDWIN-10/16/2026 @ 07:37
Clothes dryer cleaning
nl+A:tA.nnpM Are,Vi=.lA vg xn
i1141339±Eb.11%:u.+N6`W
dean flehod Pnm
a0aln
Cmnkie every snnwM mmae
-1
BRAD BALDWIN-10116/2026 @ 07:34
Fire drill completed-10/6/26
GENERATED ON 10/16/26, 8:14 AM 1 OF 6
BRAD BALDWIN-10/16/2026 @ 07:33
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
BRAD BALDWIN-1011612026 @ 07:33
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#0)-Cell:319-230-1224
BRAD BALDWIN-10/16/2026 @ 07:33
•$100 annual inspection fee
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Amy Junkin Date: BRAD BALDWIN 10116/2026
CHECKLISTS
GENERATED ON 10/16/26, 8:14 AM 2 OF 6
Additional Codes
Status Code Description
Fail 1010.2.1-Unlatching.
The unlatching of any door or leaf for Location:2 year old room-Room to bathroom exit hallway
egress shall require not require more than one operation Comments:Replace door hardware that currently requires more than
motion in a single linear or rotational direction to release all one motion to unlock and unlatch door.No more than a single(1)
latching and all locking devices.Exceptions:1.Places of motion is allowed in a required exit door.
detention or restraint.2.Where manually operated bolt locks
are permitted by Section 1010.2.5.3.Doors with automatic
flush bolts as permitted by Section 1010.2.4,Item 3 4.4.Doors
from individual dwelling units and sleeping units of Group R
occupancies as permitted by Section 1010.2.4,Item 4 5.
Fail 1010.2.1-Unlatching.
The unlatching of any door or leaf for Location:3 year old room-Room to bathroom exit hallway
egress shall require not require more than one operation Comments:Replace door hardware that currently requires more than
motion in a single linear or rotational direction to release all one motion to unlock and unlatch door.No more than a single(1)
latching and ail locking devices.Exceptions:1.Places of motion is allowed in a required exit door.
detention or restraint.2.Where manually operated bolt locks
are permitted by Section 1010.2.5.3.Doors with automatic
flush bolts as permitted by Section 1010.2.4,Item 3 4.4.Doors
from individual dwelling units and sleeping units of Group R
occupancies as permitted by Section 1010.2.4,Item 4 5.
Fail 1010.2.1-Unlatching.
The unlatching of any door or leaf for Location:4 year old room-Room to bathroom exit hallway
egress shall require not require more than one operation Comments:Replace door hardware that currently requires more than
motion in a single linear or rotational direction to release all one motion to unlock and unlatch door.No more than a single(1)
latching and all locking devices.Exceptions:1.Places of motion is allowed in a required exit door.
detention or restraint.2.Where manually operated bolt locks
are permitted by Section 1010.2.5.3.Doors with automatic
flush bolts as permitted by Section 1010.2.4,Item 3 4.4.Doors
from individual dwelling units and sleeping units of Group R
occupancies as permitted by Section 1010.2.4,Item 4 5.
Fail 1010.2.1-Unlatching.
OThe unlatching of any door or leaf for Location:5 year old room-Room to bathroom exit hallway
egress shall require not require more than one operation Comments:Replace door hardware that currently requires more than
motion in a single linear or rotational direction to release all one motion to unlock and unlatch door.No more than a single(1)
latching and all locking devices.Exceptions:1.Places of motion is allowed in a required exit door.
detention or restraint.2.Where manually operated bolt locks
are permitted by Section 1010.2.5.3.Doors with automatic
flush bolts as permitted by Section 1010.2.4,Item 3 4.4.Doors
from individual dwelling units and sleeping units of Group R
occupancies as permitted by Section 1010.2.4,Item 4 5.
Fail 807.3-Acceptance criteria and reports.
Where required to exhibit improved fire performance, Location:Throughout daycare facility
curtains,draperies,fabric hangings and other similar Comments:Provide documentation of all curtains andfor draperies
combustible decorative materials suspended from walls or meet proper flame performance criteria.Curtainsfdraperies may be
ceilings shall be tested by an approved agency and meet the treated if not currently meeting criteria to comply.
flame propagation performance criteria of Test Method 1 or
Test Method 2,as appropriate,of NFPA 701 or exhibit a
maximum rate of heat release of 100 kW when tested in
accordance with NFPA 289,using the 20 kW ignition source.
Reports of test results shall be prepared in accordance with
the test method used and furnished to the fire code official
upon request.
GENERATED ON 10/16/26, 8:14 AM 3 OF 6
Emergency Equipment
�.tus Cod( Description
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Green hallway
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress light that failed to illuminate
during test
Fail 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:Gym
in Section 1013.6.3.The system shall be capable of powering Comments:Repair or replace exit sign that failed to illuminate during
the required load for a duration of not less than 90 minutes. test
Fire Service Features
:atus Code Description
Fail 509.2-Equipment access.
Approved access shall be provided and maintained for all fire Location:4&5 year old rooms
protection system equipment to permit immediate safe Comments:Remove obstructions to fire alarm pull stations,maintain
operation and maintenance of such equipment.Storage,trash proper clearance of storage from life safety systems.
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
Fail 509.2-Equipment access.
Approved access shall be provided and maintained for all fire Location:Whale room
protection system equipment to permit immediate safe Comments:Remove obstructions to fire alarm pull stations,maintain
operation and maintenance of such equipment.Storage,trash proper clearance of storage from life safety systems.
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
GENERATED ON 10/16/26, 8:14 AM 4 OF 6
Electrical Safety
�aatas cotif Description
Fail 603.2-Abatement of unsafe conditions and electrical
hazards. Location:FACP room
Identified electrical hazards shall be abated.Identified Comments:Replace damaged outlet near electric panel
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
-11 4 , J'
•
4k �
I
Fire Resistant Construction Maintenance
si ais .cd Description
Fail 705.2.4-Door operation.
Swinging fire doors shall close from the full-open position Location:Boiler room
and latch automatically. Comments:Repair or replace fire rated door that failed to self close
and latch
Fail 705.2.4-Door operation.
Swinging fire doors shall close from the full-open position Location:Hallway-Double fire doors
and latch automatically. Comments:Repair or replace fire doors failing to self-shut and latch