COMMERCIAL FIRE INSPECTION - 710 JEFFERSON ST-10/13/26 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE # CHARGES
23382 10/20/2026 11/24/2026 2027-00000211 $80.00
Less Prepayment $0.00
Total Due - > $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
�� ) 425 E.3rd Street
The Loft-710 Jefferson ST,BLDG 710 Jefferson St-STE Upper Floor,Waterloo IA
50701
INSPECTION DETAILS
Inspection Date Inspection Type 0 Inspection Number
10/1312026 Annual Inspection(1Yr) ,� J�, 18806
Lead Inspector Shift Station Unit
BRAD BALDWIN N/A NIA NIA
Other Inspectors
N/A
SUMMARY OF INSPECTION
J44 13 ® 24
Pzs>_d cc,!,- Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 1110612026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-1011912026 @ 15:05
Stage curtains-2026.100%fire retardant polyester
FR
?!€PA 701
BRAD BALDWIN-10119/2026 @ 14:49
Christmas lighting approved for temporary(90 days)usage only.Remove lighting after 90 days has expired
BRAD BALDWIN-10/19/2026 @ 14:13
Fire extinguishers due annually serviced October 2027
BRAD BALDWIN-10/19/2026 @ 14:13
If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday—Friday,9:00 a.m.—4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
GENERATED ON 10/10/20, 3:1.3 PM 1 OF 6
inspection fees start at$100,then$150,and$200 for all subsequent re-Inspections.
BRAD BALDWIN-1011912026 @ 14:13
•Provide corrections to avoid progressive re-inspection tees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-10119/2026 @ 14:12
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(40)-Cell;319-230-1224
BRAD BALDWIN-10/19/2026 @ 14:12
•$80 annual inspection fee
SIGNATURES
Contact signature Inspector signature
No signature }
Report completedeelpost stinspection `1
Dana Dzick(2026) Date: BRAD BALDWIN 10119/2026
CHECKLISTS
Emergency Equipment
c`a:'" Description
Fail 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:Front exit-High bay exit sign
in Section 1013.6.3.The system shall be capable of powering
Comments:Provide document indicating exit sign has been tested
the required load for a duration of not less than 90 minutes. and functioning properly
Fail 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:Near bar
in Section 1013.6.3.The system shall be capable of powering Comments:Remove Halloween decorations draped over exit sign
the required load for a duration of not less than 90 minutes.
Fire Sprinkler System
Status Co:: Description
Fail 4.9-Support of nonsprinkler system components
Sprinkler system components shall not be used to support Location:Above"Sam Adam's"mirror
non-sprinkler system components unless expressly permitted Comments:Remove HDMI cord hanging sprinkler
by NFPA 13. 9 9 on p piping
Fail 4.9-Support of nonsprinkler system components
L 1 Sprinkler system components shall not be used to support Location:Near stage
non-sprinkler system components unless expressly permitted Comments:Remove speaker wire being supported by sprinkler
by NFPA 13.
piping.
GENERATED ON 10/1G/26, 3:23 PM 2 of 6
Additional Codes
Status Code Description
Fail 5303.5.3-Securing compressed gas containers,cylinders
and tanks. Location:Bar
Compressed gas containers,cylinders and tanks shall be Comments:Secure tanks to avoid tip-over hazard.
secured to prevent falling caused by contact,vibration or
seismic activity.Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers,cylinders and tanks to a fixed object
with one or more restraints.2.Securing containers,cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers,cylinders or tanks.
3.Nesting of compressed gas containers,cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public.Nesting shall be allowed
provided that the nested containers,cylinders or tanks,if
dislodged,do not obstruct the required means of egress.
4.Securing of compressed gas containers,cylinders and
tanks to or within a rack,framework,cabinet or similar
assembly designed for such use.Exception:Compressed gas
containers,cylinders and tanks in the process of
examination,filling,transport or servicing.
Fail 907.8.1-Maintenance required.
Where required for compliance with the provisions of this Location:Fire alarm
code,devices,equipment,systems,conditions, Comments:Deficiency(see attachment)shall be corrected including
arrangements,levels of protection or other features shall contractors repair report to be uploaded to Compliance Engine.
thereafter be continuously maintained in accordance with
applicable NFPA requirements or as directed by the fire code
official.
GENERATED ON 10/19/26, 3:13 PM 3 OF 6
Electrical Safety
Std'-us Code Description
Fail 603.5.2-Application and usePower supply.
Relocatable power taps and current taps shall be directly Location:"Boulevard Brewing"sign
connected to a permanently installed receptacle.Exceptions: Comments:Power strip above sign"daisy chained"shall be removed
1.Where approved for use in a Group A occupancy or Ina to be plugged directly to a permanent outlet
meeting room in a Group B occupancy,not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment.2.Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
Fail 603.5.2-Application and usePower supply.
Relocatable power taps and current taps shall be directly Location:Stage
connected to a permanently installed receptacle.Exceptions: Comments:Remove power strip plugged to multi-plug adapter,
1.Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy,not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment.2.Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
c
0
v /
;-,'' . may. *I z + ;
rifry � 2
t i ''";fi 'Eye, 2 4
CS"_ f
1: t 'S�s � rsba
t
Fail 603.5.3-Installation.
Relocatable power tap cords shall not extend through walls, Location:Gambler games
ceilings,floors,under doors or floor coverings,or be subject Comments:Properly mount power strip above games to avoid
to environmental or physical damage. hanging by wires
GENERATED ON 10/10/26, 3:13 PM 4 OF 6
Fall 603.6-Extension cords.
0 Extension cords and flexible cordsshall not be a substitute Location:Back closet
for permanent wiring and shall be listed and labeled In Comments:Remove extension cords.
accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical Impact.Extension cords shall be used only with
portable appliances.Extension cords marked for Indoor use
shall not be used outdoors.
Fail 603.6•Extension cords.
0 Extension cords and flexible cordsshall not be a substitute Location:Near stage
for permanent wiring and shall be listed and labeled in Comments:Remove black extension cord
accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Near"Sam Adam's"neon sign
for permanent wiring and shall be listed and labeled in Comments:Remove extension cord
accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Near sound board
for permanent wiring and shall be listed and labeled in Comments:Remove extension cords(2)
accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
GENERATED ON 16/10/26, 3:13 PM 5 OF 6